- Portable & Packaged Chillers Air & Water Cooled
- >
- TempTek Portable Water Chillers
- >
- TempTek Air-Cooled Liquid Portable Chillers
- >
- TempTek CF-30A 30 Ton Portable Air-Cooled Water Chiller
TempTek CF-30A 30 Ton Portable Air-Cooled Water Chiller
SKU:
CF-30A
$0.00
On Sale
Unavailable
per item
**CALL FOR PRICING QUOTE {815-385-2350}**
​AVAILABILITY UPON QUOTE REQUEST
- Portable chillers use mechanical refrigeration to cool recirculated fluids that support industrial process cooling applications.
- Portable chillers include an internal pumping system and reservoir system.
- Portable chillers can be moved between use points as needed.
- Air-Cooled chillers use indoor ambient air to dissipate the heat from the refrigeration system.
Sold out
Specifications:
Capacity: (2) Tons : 29 kW : 101.8
Compressor: HP : 30 Type : Scroll
Process Pump: HP : 5 GPM : 72 PSI : 57
Type: Centrifugal
Construction : Stainless Steel
Automatic Low Flow Bypass: : Standard
Air-Cooled Condenser: Type : Blower CFM : 30,000 (6) SP : 1.35 (3) Ambient : 95°F
Refrigerant: Type: R-410A
Full Load Amperage (4): 230/3/60 : 192 460/3/60 : 96 575/3/60 : 77
Reservoir Capacity: Holding : 65 gal Lid : Standard Auto Make-Up : Optional
Process Connections: To Process : 2" From Process : 2" Make-Up : 1/2"
Dimensions: Height : 96" Width : 58" Depth : 70"
Weight (5): Shipping : 3,500 lbs
Specification Notes:
Capacity: (2) Tons : 29 kW : 101.8
Compressor: HP : 30 Type : Scroll
Process Pump: HP : 5 GPM : 72 PSI : 57
Type: Centrifugal
Construction : Stainless Steel
Automatic Low Flow Bypass: : Standard
Air-Cooled Condenser: Type : Blower CFM : 30,000 (6) SP : 1.35 (3) Ambient : 95°F
Refrigerant: Type: R-410A
Full Load Amperage (4): 230/3/60 : 192 460/3/60 : 96 575/3/60 : 77
Reservoir Capacity: Holding : 65 gal Lid : Standard Auto Make-Up : Optional
Process Connections: To Process : 2" From Process : 2" Make-Up : 1/2"
Dimensions: Height : 96" Width : 58" Depth : 70"
Weight (5): Shipping : 3,500 lbs
Specification Notes:
- 1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
- 2. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ " 115°F condensing temperature. Capacities may be +/- 5% as reserved by the compressor manufacturer. Operating at temperatures below 50° will reduce chiller capacity. The minimum recommended operating temperature when no glycol is used is 48°F.
- 3. Design ambient conditions. Loss of capacity and/or difficulty operating will occur at higher ambients. Minimum recommended ambient is 60°F.
- 4. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring.
- 5. Approximate unit weight crated for shipment.
- 6. Static pressure in inches of water.
Options:
Refrigerant Circuit
|
Coolant Circuit
|